Key Features
LED indicator for trouble-shooting, correct wiring or locating product
Wide selection of differential pressure ranges
Field-selectable output (voltage version)
3-year warranty
DIN Rail Mount is standard
Compact, rugged construction
Excellent long term stability
High overpressure limit
TruAccuracy™ performance ensures the transducer meets its rated accuracy out of the box and is ready for installation with no additional calibration adjustments required.
Markets & Applications
HVAC-R
Duct Flow
Comfort Control Systems
Filter Monitoring
Blower Performance
Pharmaceuticals
Fume Hood Control
Critical Environments
Clean Room / Laboratory Pressurization
Accuracy
0.4% of span
0.8% of span
0.25% of span
Pressure Type
Differential pressure
Static Pressure
1.7 bar / 25 psi
Electrical Termination
Euro style pluggable terminal block
Output Signal
4-20 mA (2-wire)
0-5 VDC (3-wire)
0-10 VDC (3-wire)
Ranges
Bidirectional: ±12.5 Pa ... ±12.5 kPa / ±0.05 in. H2O ... ±50 in. H2O
Unidirectional: 25 Pa ... 25 kPa / 0.1 in. H2O ... 100 in. H2O
Wetted Parts Material
Aluminum, Titanium, PBT, Buna, Glass, Gold, Silicone Rubber, Silicon, Silicone RTV & Brass. NOT FOR USE WITH LIQUIDS
Ingress Protection
NEMA 1
Case or Body Material
Fire-retardant ABS
Stability
≤±0.25% span/year at reference conditions
Mounting
DIN rail
Surface
Process Connection Style
Barbed fitting
Threaded
Equipped with a highly reliable and accurate sensing element, featuring the patented Ashcroft® Si-Glass™ sensor, Ashcroft offers a range of differential pressure transmitters specifically designed and developed for use in the cleanroom industry. Using an ultra-thin single crystal diaphragm, Ashcroft differential pressure transmitters offer inherent sensor repeatability and stability, making them stand out as highly accurate, long-term stable and reliable measurement instruments for cleanroom pressure monitoring.
The silicon diaphragm sensor is free of adhesives or other organic materials that are commonly used in differential pressure measurement technology and contribute to a drift in the measured value acquisition or a mechanical reduction in the measurement accuracy.
Ashcroft differential pressure transmitters incorporate the TruAccuracy™ specification. Ashcroft’s accuracy claim is based solely on terminal endpoint methodology and not on statistically derived accuracy claims’.
TruAccuracy™ means that Ashcroft differential pressure transmitters include zero offset, non-linearity, hysteresis, non-repeatability, zero offset and span adjustment error in their accuracy statement.
The user thus has a ready-to-install device at his disposal that does not require any initial calibration after installation. This considerably reduces the time and costs involved.
Other commercially available measuring devices usually do not include information on zero point deviation and span error in their accuracy specifications, so that these measurement errors (up to ±1.00%) must be added to the accuracy in order to achieve reliable performance characteristics.