Key Features
Min. / Max. function records low and high pressure events
Easy local adjustments using 3 pushbuttons
Ultra-compact design
3-in-1 capability: digital pressure gauge, switch and transducer
Programmable switch setting and analog scaling
Simple Push-button menu navigation
Markets & Applications
Dampening
Digital by firmware setting
Process Connection Style
Barbed fitting
Accuracy
1.5% of span (URL)
Pressure Type
Differential pressure
Switch Style
NPN or PNP - Field programable
Static Pressure
500 mbar / 7.5 psi
Ranges
Unidirectional: 50 Pa ... 5 kPa / 0.25 in. H2O ... 25 in. H2O
Bidirectional: ±50 Pa ... ±5 kPa / ±0.25 in. H2O ... ±25 in. H2O
Wetted Parts Material
Aluminum, Titanium, PBT, Buna, Glass, Gold, Silicone Rubber, Silicon, Silicone RTV & Brass. NOT FOR USE WITH LIQUIDS
Ingress Protection
IP40
Display
3½ digit LED
Case or Body Material
Polycarbonate/ABS
Process Connection Location
Centre back
Electrical Termination
Wire leads, PVC insulated
Mounting
Flush
Surface
Output Signal
1-5 VDC (3-wire)
Equipped with a highly reliable and accurate sensing element, featuring the patented Ashcroft® Si-Glass™ sensor, Ashcroft offers a range of differential pressure transmitters specifically designed and developed for use in the cleanroom industry. Using an ultra-thin single crystal diaphragm, Ashcroft differential pressure transmitters offer inherent sensor repeatability and stability, making them stand out as highly accurate, long-term stable and reliable measurement instruments for cleanroom pressure monitoring.
The silicon diaphragm sensor is free of adhesives or other organic materials that are commonly used in differential pressure measurement technology and contribute to a drift in the measured value acquisition or a mechanical reduction in the measurement accuracy.
Ashcroft differential pressure transmitters incorporate the TruAccuracy™ specification. Ashcroft’s accuracy claim is based solely on terminal endpoint methodology and not on statistically derived accuracy claims’.
TruAccuracy™ means that Ashcroft differential pressure transmitters include zero offset, non-linearity, hysteresis, non-repeatability, zero offset and span adjustment error in their accuracy statement.
The user thus has a ready-to-install device at his disposal that does not require any initial calibration after installation. This considerably reduces the time and costs involved.
Other commercially available measuring devices usually do not include information on zero point deviation and span error in their accuracy specifications, so that these measurement errors (up to ±1.00%) must be added to the accuracy in order to achieve reliable performance characteristics.